Gratings in data centres: more air, more load, less downtime
Cooling is the biggest operating cost in a data centre – and the air outlet in the cold aisle is often the bottleneck. Custom gratings provide 70–80 % free area, carry server cabinets and pallet trucks and fit any grid. The essentials for planners and operators.
1. Free area: why a grating outperforms perforated plate
Depending on type, perforated raised-floor panels have 25 to 56 % open area; a 30/30 press-locked grating is at around 80 %, 30/10 at around 70 %. For the same panel area, up to twice as much cold air flows into the cold aisle – or the same volume flow at a considerably lower pressure drop. This reduces the fan power of the CRAC/CRAH units and eases hotspots in the upper rack units. Where the air flow is to be directed (air towards the rack fronts instead of straight up), louvre gratings with angled louvres are used.
2. Where gratings are used in data centres
- Air outlets in the cold aisle: gratings in the 600 × 600 grid instead of perforated panels, with mesh 30/10 against falling small parts.
- Covers for cable and air-conditioning ducts in floor ducts, along rack rows and in plant areas – walkable, with cut-outs for cable trays and columns.
- Walkable floors over cooling coils and dry coolers (roof, plant yard) – maintenance areas with full air flow.
- Mezzanine floors and walkways in ventilation plant rooms, transformer and UPS rooms, battery rooms (stainless steel or powder-coated here).
- Ventilation gratings in façade and plinth for free cooling – louvre gratings against rain and prying eyes.
- Ramps and steps to raised-floor areas with nosing (grating stair treads).
3. Loads: server cabinets, pallet trucks, engineering teams
Raised floors in data centres are often designed for point loads of 5 to 10 kN per foot and distributed loads of around 10 to 20 kN/m². Depending on its configuration, a fully loaded server cabinet can weigh well over a tonne, spread over four feet or castors; add to that pallet trucks and trolleys during rollout. For gratings this means:
| Case | Point load | Bearing bar at 600 mm span | Bearing bar at 1000 mm |
|---|---|---|---|
| Pedestrian only (maintenance) | 1.5 kN | 25 × 2 | 30 × 2 |
| Trolleys, light racks | 5 kN | 40 × 2 | 50 × 3 |
| Pallet truck, heavy racks on feet | 10 kN | 50 × 3 | 50 × 5 |
| Rollout with pallet truck | up to 16 kN | 50 × 5 | 60 × 5 |
Values from the bearing bar table to RAL-GZ 638; deflection ≤ L/200. Because racks often stand on hard levelling feet with a small contact area, we check load introduction on 200 × 200 mm for project enquiries and recommend load-spreading plates or a closer pitch where needed.
4. The right specification
| Feature | Data centre recommendation | Why |
|---|---|---|
| Type | Press-locked grating (P) | flat pattern, exact dimensions, fine mesh possible |
| Mesh | 30/10 (33/11); 30/30 where only airflow counts | screws, cable ties and tools do not fall into the floor |
| Bearing bar | 30 × 3 to 50 × 3 | racks and pallet trucks (see table) |
| Finish | hot-dip galvanised; 304 stainless steel or duplex powder coating in dust-critical rooms | abrasion-resistant, no zinc dust, appearance |
| Slip resistance | smooth (R10) | serrations cause abrasion and dust – undesirable |
| Dimensions | raised-floor grid 600 × 600 mm, any duct width, cut-outs to floor plan | fits existing systems |
| Installation | frame or support in the raised-floor system, clips against lifting | DGUV 208-007, no slipping during rollout |
| Equipotential bonding | earth the grating via frame/substructure | steel grating is conductive – an advantage over GRP for ESD concepts |
| Fire protection | steel, material class A1 | non-combustible, no smoke gases – unlike GRP |
5. Project handling: parts list instead of single orders
A data centre rarely needs one grating; it needs hundreds of panels in ten variants. For that:
- Enquiry with floor plan / grid plan via the contact form – we draw up the parts list with position numbers.
- Marking of each grating with its position number (tag or embossing), delivery packed by room and row.
- Documentation: declaration of conformity RAL-GZ 638 / DIN 24537-1, proof of load capacity, zinc coating report on request – for FM handover and certifications.
- Repeat orders: identical gratings at any time via the position number, even years later.
- Individual panels and duct covers with an instant price directly in the configurator.
Questions and answers
Why gratings instead of perforated raised-floor panels?
A grating has 70–80 % free area, a perforated plate 25–56 %. For the same area, considerably more cold air flows at a lower pressure drop – less fan power, fewer hotspots.
Which mesh makes sense in a data centre?
30/10 (pitch 33/11): screws, cable ties and tools do not fall into the raised floor, yet there is still around 70 % open area. 30/30 where only airflow counts.
Can a grating carry a server cabinet?
Yes – with a 600 mm grid and a 10 kN point load, a 50×3 bearing bar is sufficient, 50×5 for 16 kN. For hard levelling feet with a small contact area, we check load introduction and recommend load-spreading plates where needed.
Do gratings fit an existing raised-floor system?
Yes, we manufacture to the 600×600 mm grid (or any other) with the right build-up height and cut-outs; resting on the stringers or in a frame.
Can louvre gratings direct the air?
Yes. Angled louvres direct the air flow towards the rack fronts; angle and direction as specified by the cooling concept.